Permit Number: TC-RES-0825-03985
Parcel: 124170380

Address:
716 S FREMONT AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADD/ALT v.1

Permit Number - TC-RES-0825-03985
Review Name: RESIDENTIAL ADD/ALT v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/11/2025 Residential Building - Standard APPROVED 1. All construction shall comply with the International Residential Code (IRC) 2018 and Pima County local Amendments.
2. All Concrete shall be a minimum of 2500 psi.
3. All Wood to be #2 Douglas Fir or better.
4. Framing based on 30 lbs load.
5. Minimum Ceiling Height 7’, 6’-6” to beam.
6. Maximum post height shall be 10’ from finished grade. (Or provide engineering)
7. Soil bearing pressure minimum1500 psf. (Table R401.4.1)
09/16/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/16/2025 Site Zoning - Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Krista Hansen
Planning & Development Services Department – Zoning Review Section

PROJECT: TC-RES-0825-03985
716 S FREMONT AV
Residential Alteration (1st Review)

TRANSMITTAL DATE: 09/16/2025


This site is located in the R-2 zone (UDC 4.7.9). A single-family residence is a permitted use in this zone subject to use-specific standards 4.9.7.B.6, .9 and .10.


Resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed.

01. COMMENT: The Lot Area is incorrect. Calculate area using lot dimensions (50 ft. x 185 ft.).

02. COMMENT: The Side and Rear Yard setbacks listed under Project Information are incorrect. Per Unified Development Code (UDC) Table 6.3-2.A, side and rear setbacks are 6' or 2/3 the height of the adjacent building wall.

03. COMMENT: Remove porch from lot coverage calculation, as roofed areas, open on at least one side, which provide shelter to exterior areas, are not included in the lot coverage calculation (UDC 6.4.3.C.1.a).

04. COMMENT: On the building elevations, add wall height as measured from design grade to the highest point of the exterior wall (UDC Article 6.4.5.B & Figure 6.4.5-A), and dimension building height as measured from design grade to the middle (between the eave and ridge) of the highest gable of the hipped roof.


The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code


For questions regarding Zoning comments, please contact me at: Krista.Hansen@tucsonaz.gov
08/13/2025 PDSD Application Completeness Express REVIEW COMPLETED