Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.3
Permit Number - TC-RES-0825-03833
Review Name: RESIDENTIAL SIMPLE REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/08/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/08/2025 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | PDSD Residential Review Section PROJECT: TC-RES-0825-03833 Main panel upgrade-(1st Review) (1224 N BEDFORD PL) TRANSMITTAL DATE: August 8th, 2025 Comments: 1. No permit history for the solar installation. Please provide permit it was done under. 2. A PV disconnect is required to be installed within 10 feet of the service entrance: Show compliance with NEC 690.15(A), PV solar Disconnect Switch is greater than 10’ from the service entrance. 3. Either show permitted solar installation and disconnect in the code compliant location, or submit only for the service upgrade/replacement. Any questions email building_official@tucsonaz.gov |
||
| 08/07/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |