Permit Number: TC-RES-0824-05032
Parcel: 106021720

Address:
231 W SMOOT DR

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0824-05032
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2024 Site Engineering NOT REQUIRED
09/30/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/16/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0824-05032 (231 W SMOOT DR TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).


1. After a review of aerial views (https://maps2.tucsonaz.gov/Html5Viewer/?viewer=maptucson#) of the property, it appears that PV modules are mounted on an unpermitted porch structure on the back of the main house. Searching city records through PRO (https://pro.tucsonaz.gov/address_search/) found no permit history for this structure. Either provide completed permit and inspection documentation, apply for and complete permit review and inspections for the structure or remove the PV modules from the unpermitted structure.
2. Aerial views of the property show the overhead service conductors passing over the roof of the unpermitted porch structure. The overhead service conductor over the structure requires an 8’ clearance above the roof, E3604.2.1. The 8’ clearance is required to be maintained for a distance of 3’ from the edge of the roof. Show a mast height necessary to achieve this clearance. Check with TEP customer service for service line options. https://www.tep.com/electric-service-requirements


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov