08/27/2024 Light Residential Building Review (OIP) APPROVED Approved with the following comment:
The overhead service conductor over the structure requires an 8’ clearance above the roof, E3604.2.1. The 8’ clearance is required to be maintained for a distance of 3’ from the edge of the roof.