Permit Number: TC-RES-0824-04809
Parcel: 131030450

Address:
5202 E 24TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.4

Permit Number - TC-RES-0824-04809
Review Name: RESIDENTIAL NEW DWELLING v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2024 Site Engineering APPROVED
10/14/2024 Site Landscape NOT REQUIRED
11/14/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
10/22/2024 Residential Building REQUIRES RESUBMIT TC-RES-0824-04809 2nd
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance. The plans require sufficient detail for showing minimum building code compliance for passing all progress inspections.

Provide a response letter on separate file with the updated construction plan set.

PLANS:

1. Clarify that the existing roof truss system has no interior bearing walls or provide an engineer’s sealed plan set for sizing a beam at the removed kitchen wall, R301.1.3.
2. Show the door from a garage to dwelling with a 20-minute fire rating (or 1-3/8” solid core) with self-closing and self-latching provision, R302.5.1.

SECTIONS - DETAILS:

1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF. Provide a proposed bedroom ceiling/roof insulation detail showing the air-impermeable rigid insulation material adhered to either side of the roof sheathing and the batt insulation in contact with the roof material.

PLUMBING PLANS:

1. Show the required drain and vent for the proposed washer/dryer on sheet A-3, P2602.1.
2. Update fixture keynote #8 showing the tankless water heater rating, P2801.1.
3. Show a gas pipe sized for the water heater demand in conformance with Table G2413.4(1). Existing gas pipes may require upgrading with this system alteration. Provide a gas (1,000 BTUh = 1 CFH) conversion coordinated with Southwest Gas. Also, provide the developed length for each appliance.

MECHANICAL PLANS:

1. Clarify the cooling capacity in accordance with M1401.3, M1601.1. The 4-ton cooling unit may be oversized for the dwelling demand.

ELECTRICAL PLANS:

1. Show a smoke alarm in each bedroom and outside the doorway in the immediate vicinity, R314.3. Relocate the detector from the garage and show a device in each hallway.
2. Garage Branch Circuit: a separate (dedicated) GFCI 20-amp branch circuit required for receptacles in an attached garage, E3703.5.

OUTDOOR LIGHTING CODE

1. Show full cutoff (FCO) fixtures were located within 25 feet from the property line OLC 401.3.3. Replace the fixture B symbol with a shieled unit which cannot illuminate horizontally. Adjustable security light fixtures are unshielded, not FCO.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
----------------------
11/14/2024 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Bobby Parsons
Zoning Section Review

PROJECT: TC-RES-0824-04809
5202 E 24th Street Tucson, AZ 85711
Renovate SFR and enclose garage into bedroom (2nd Review)

TRANSMITTAL DATE: 11/14/2024

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 - .9.

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: The site plan should be designed to include the information as noted on the sample site plan. Please see https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/residential_plot_plan_requirements.pdf for reference.
2. Comment: Please label the surrounding zoning classification.
3. Comment: Please use the correct legal description which should read: Mayfair Terrace NO 2 Lot 45.
4. Comment: Please label the centerline to the face of curb and from face of curb to the property line along 24th Street.
5. Comment: Please dimension the rear alley.
6. Comment: Please draw, dimension, and label the vehicular use area on the site plan.
7. Comment: Please update the zoning classification under project data. Currently, plans state property is zoned R-3 which is incorrect.
8. Comment: The setbacks under project data are listed incorrectly. The rear yard setback for the R-1 zone is 6’ or 2/3 Height of the wall. Currently your plans have 10’ listed as the rear yard setback.
9. Comment: Additional comments may be forthcoming based on responses to zoning comments and changes made to the plans.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov (520) 837-4977.
10/14/2024 PDSD Application Completeness REVIEW COMPLETED