Permit Number: TC-RES-0824-04782
Parcel: 11904272A

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0824-04782
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2024 Site Engineering NOT REQUIRED
09/16/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/03/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES -0824-04782
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. The #2 AWG conductor (tag 4 & 5) is undersized for the given OCPD (125A).
2. Maximum conductor ampacity is determined by applying correction and adjustment factors for temperature of insulation rating of 90C and CCC (Current Carrying Conductor) proximity. Reference NEC 310.15, Table 310.15(B)(2)(a), 310.15(B)(2)(b) and 310.15(B)(3)(a). The adjusted conductor rating may not be less than the given OCPD.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov