Permit Number: TC-RES-0824-04701
Parcel: 111064070

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0824-04701
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/19/2024 Residential Building REQUIRES RESUBMIT TC-RES-0824-04701
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments and building ordinances for all dwellings.

Provide a response letter on separate file with the updated construction plan set.

Clarify if the Guest House will be a sleeping quarters (without kitchen) or an Accessory Dwelling Unit (ADU) which requires many alterations for compliance.

Each dwelling unit with kitchen requires a separate Pima County assigned street address after Zoning approval, R319. Show Pima County assigned unit numbers at each dwelling on the site plan. https://www.pima.gov/1010/Addressing-Frequently-Asked-Questions

An impact fee payment is required for an ADU at the time of permit payment.

SITE PLAN:

1. Show the location of the electrical service line between the TEP source and the service panel, R106.1.1. Show the location of the water meter. Identify the utility lines requiring upgrade or replacement.

PLANS:

1. Notate a cool (white) roof finish (greater than 60 SRI) as required by the ADU provisions.

SECTIONS – DETAILS -- NOTES:

1. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground (R317.1 item 5). The weep screed may extend with a minimum clearance 4” above grade or 2” above paved areas, R703.7.2.1. Update detail #1 on A3.0.
2. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF. Clarify the ceiling/roof insulation detail showing the air-impermeable rigid insulation material adhered to either side of the roof sheathing and the batt insulation in contact with the roof material.

PLUMBING PLANS:

1. Show the sink trap arm size and connection point as required by P3201.7.
2. Show plumbing vents (VTR) within acceptable distances from traps, P3105.1.

MECHANICAL PLANS:

1. Show the HVAC system size for the building demand in accordance with M1401.3, M1601.1.
2. Show a bathroom (without a window) exhaust fan with minimum 50 CFM rating and duct to the exterior, R303.3 and M1505.
3. Show the kitchen exhaust fan minimum 100 CFM rating, M1505. Update keynote #5.

ELECTRICAL PLANS:

1. TEP may require the service panel for the property at the closest building to the service transformer. A service line change or a new meter location must be coordinated with TEP for approval. Show an underground feeder from a metered service panel to the more distant dwelling.
2. Update the Riser Diagram showing the main service and the feeder size to the detached dwelling panel per TEP coordination, NEC 225.30 and E3403.
3. Provide a minimum service conductor rating of #3 copper 75 degree C for the 100 AMP feeder, E3602.1 & E3603.1.
4. Notate the replacement of the 50 AMP panel with a 100 AMP panel at keynote #1.
5. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm in each bedroom and outside the doorway in the immediate vicinity.
6. Interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights, and smoke detectors require combination type arc-fault circuit interrupters, E3902.16. Add notation to plans.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/pdsd
09/12/2024 Site Engineering REQUIRES RESUBMIT 1. This project is in a regulated floodplain and requires a floodplain use permit. For the floodplain use permit, please provide (1) a PDF cost estimate for materials and labor for the project and (2) the plans showing the finished flood elevation (FFE) for the guest house.

Mike Ortiz
michael.ortiz@tucsonaz.gov
09/12/2024 Site Landscape REQUIRES RESUBMIT CDRC TRANSMITTAL
PLANNING AND DEVELOPMENT SERVICES DEPARTMENT
REVIEWER: CHAD KELLER, RLA
PDSD SITE LANDSCAPE/NATIVE PLANT PRESERVATION SECTION

Site Landscape/NPPO Section Review Comments:

1. Ensure that zoning and engineering comments are addressed prior to site landscape approval.

2. If protected native plants are going to be disturbed or removed, then please provide a NPPO or a NPPO Waiver for the area of work being done with the addition. If a copy of the NPPO Waiver is needed, please reach out and I will email a copy for your use.

Thank you.
Chad Keller, RLA
chad.keller@tucsonaz.gov
09/10/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-RES-0824-04701
2801 N SPARKMAN BL. – R-2
Convert Sleeping Quarters to 2nd Dwelling Unit (1st Review)

TRANSMITTAL DATE: September 10, 2024

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-2 zone (UDC 4.7.9). A two (2) single-family residence (SFRs) are permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6,.9, & .10.

1. The lot coverage calculation is not correct. Review UDC Article 6.4.3 and the example shown on the Residential Plot Plan Requirements found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Plan-Examples/Plot-Plan-Example, and provide a correct lot coverage calculation.

2. The property dimensions are not correct. Review the Assessor’s Record Map found at: https://www.asr.pima.gov/ParcelData/Map/Arm/MP06/06058_05.PDF, and provide the correct dimensions.

3. Based on aerial photographs there is a structure located in the southeast corner of this parcel not shown on the plot plan. Clearly show all structures on the plan and if applicable include the structures in the lot coverage calculation.

4. Remove the setback lines shown on the plot plan as they are not correct.

5. Sheet A2.0 clarify how you can have two (2) north elevations that do not match.

6. Provide a dimension from centerline of Glenn St. to the northern most face of curb and from face of curb to the property line. Per Construction plan I-80-032 found at: https://maps-and-records.tucsonaz.gov/construction-plans/details/I-80-032, the distance from centerline to face of curb is 22’ and from face of curb is 8’-0”.

7. Provide a dimension from centerline of Sparkman Ave. to the face of curb and from face of curb to the property line. Per Construction plan I-80-032 found at: https://maps-and-records.tucsonaz.gov/construction-plans/details/I-80-032, the distance from centerline to face of curb is 18’ and from face of curb is 12’-0”.

8. As Glenn St. is designated as a Collector on the COT MS&R map and has a future half right-of-way of 32’show the future right-way-line on the plan and provide a setback dimension from the proposed addition to the future right-of-way line.

9. Per UDC Article 6.4.5.C.1.b the required street perimeter yard setback from the proposed addition to the south property line is 10’-0”. Based on the future right-of-way line called out in comment 8 the proposed setback is 6’-6”. A Design Development Option (DDO) must be submitted and approved to reduce the required setback. DDO application and requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration. If you have questions about the DDO application or process please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov or Georgia Pennington at Georgia.Pennington@tucsonaz.gov.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/13/2024 PDSD Application Completeness Express REVIEW COMPLETED