Permit Number: TC-RES-0824-04648
Parcel: 133311050

Address:
8838 E COOPER ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0824-04648
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2024 Fire New Construction NOT REQUIRED
09/10/2024 Site Engineering NOT REQUIRED
09/12/2024 Site Landscape NOT REQUIRED
09/12/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/15/2024 Residential Building REQUIRES RESUBMIT TC-RES-0824-04648
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes.

Provide a response letter on separate file when submitting the updated construction plan set.

Show a page number on each sheet of the plan set.

Provide a clear and concise construction plan set. Sample drawings for the Garage Sample. Sample plans are available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits

SITE PLAN:

1. Show the location of the electrical service panel and area of enclosed carport, R106.1.1.

PLANS:

1. Clarify if the wall separating the dwelling from the proposed garage has any window of door openings, R302.5.1. Any openings require fire rated covering.
2. Show the location of each support footing at new wall locations, R106.1.1.

SECTIONS - DETAILS:

1 Show reinforced footing dimensions required for post/beam construction, R403.1.1.
2 Show pressure treated sill anchored with ½” x bolts providing 7” embedment. Show the wall assembly with a 6” clearance above the ground or 2” clearance above an exterior concrete surface, R317.1 item 5.
3 Specify veneer anchoring with ties spaced 24” O.C. horizontally & vertically, R703.2 & R703.7.
4 Show 1” air space between sheathing and veneer R703.8.
5 Show method of flashing beneath the first course of veneer (R703.7.5) with weep holes (R703.7.6).
6 Identify all fasteners between wall and sill plates (H2.5), R802.11 amended.

ELECTRICAL PLANS:

1. Garage Branch Circuit: a separate (dedicated) GFCI 20-amp branch circuit required for receptacles in an attached garage and detached garages with service, E3703.5. A receptacle is required at each vehicle bay not more than 5.5 feet above the floor, E3901.9.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review
09/09/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-RES-0824-04648
8838 E COOPER ST. – R-1
Enclose Carport into Garage (1st Review)

TRANSMITTAL DATE: September 9, 2024

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 – 9

1. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Plan-Examples/Plot-Plan-Example.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/09/2024 PDSD Application Completeness Express REVIEW COMPLETED