Permit Number: TC-RES-0824-04625
Parcel: 134050610

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0824-04625
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2024 Site Engineering NOT REQUIRED
09/10/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/14/2024 Residential Building REQUIRES RESUBMIT TC-RES-0824-04625
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Facilitate a shorter back check time: provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance.

Provide a response letter on separate file with submitting the updated construction plan set.

Provide a clear and concise construction plan set. Sample drawings for Garage are available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits

SITE PLAN:

1. Indicate the location and size of the electrical service panel, R106.1.1.

PLANS:

1. Show the room function with a door opening into the proposed garage. Openings from a garage directly into a sleeping room are not permitted, R302.5.1.
2. Show the material composition of the wall separating the garage and dwelling. This wall requires a fire rated product in compliance with R302.6 such as ½” gypsum board (garage side).
3. Provide a Roof Framing Plan showing the location and size of the mid-span beam for supporting live and dead structural loads of rafters and trusses, R804.

STRUCTURAL PLANS:

1. Adobe block is not a prescriptive material recognized by the 2018 IRC, R106.1.1. Provide an engineer’s calculation, design, and seal for a performance design when not code compliant with the IRC, R301.1.

SECTIONS - DETAILS:

1 Identify top plate to rafter and truss fasteners for wind loading compliance. Show roof (uplift resistance) fasteners (H2.5) with appropriate uplift capacity, R802.11 amended.

ELECTRICAL PLANS:

1. Show the garage branch circuit as a separate (dedicated) GFCI 20-amp size, E3703.5.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review
09/06/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-RES-0824-04625
624 S SANTA ANA DR – R-1
Garage Addition (1st Review)

TRANSMITTAL DATE: September 6, 2024

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 – 9

1. The lot coverage calculation is not correct. Per UDC Article 6.4.3.C.1.a Roofed areas, porches, open on at least one side are not included in the calculation. Also swimming pools are not included.

2. The northeast property line dimension is not correct and per the Hermosa Hills Estates final plat the dimension should be 149.93’.

3. Provide a dimension from the centerline of Sanatana Pl. to the face of curb, where pavement meets the concrete, and from face of curb to the property line for both Placita Toluca & Avenida De La Tula.

4. Provide a dimension from the property line along Sanatana Pl to the proposed garage.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/08/2024 PDSD Application Completeness Express REVIEW COMPLETED