Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0823-07686
Parcel: 111074430

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0823-07686
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/18/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT ROM: Veronica Flores
PDSD Residential Review Section

PROJECT: TC-RES-0823-07686
PV solar roof mount 26 panels 10.4 kW DC-(1st Review)
(3356 E Popinac Lp)

TRANSMITTAL DATE: September 19th, 2023

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a Written Response Letter to each of the notated items indicating action taken. Resubmitted plans/calculations that do not contain a written Response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

COMMENTS: Code reference, 2018 International Residential Code (IRC).

1. Provide electrical load calculations for the subpanel showing the solar backfeed will not backfeed to the main panel, E3602.2, or Provide Main Service Panel (MSP) taps in compliance with NEC 705* (NEC 705.12) 705.12(B)(2)(3) b Busbars.) 120% bus bar rule.

If you have any questions about this transmittal, Contact Veronica Flores by email Veronica.Flores@tucsonaz.gov
09/05/2023 Site Engineering REQUIRES RESUBMIT Project: TC-RES-0823-07686

Address: 3356 E POPINAC LP

This project is within a regulated floodplain and requires a Floodplain Use Permit (FUP.)

Please start a new FUP at our permit application web page:

https://tdc-online.tucsonaz.gov/#/home

NOTE: Documentation of a cost estimate from your contractor will be required if this project involves any reconstruction, repair, rehabilitation, structurally connected addition, or other improvement of an existing structure (including TI’s and solar). Construction of separate builds/new structures does not require a cost estimate to be provided.

Instructions:

1. Navigate into the current project in the “My Work” tab. Within the permit, navigate to the “Sub-Records” tab and click “Apply” on the Floodplain Use Permit Sub-Record

2. Locations -> Confirm the location is accurate to the project. Click “Next”

3. Type -> Fill in the “Square Feet” and “Valuation” boxes with the project area and a contractor-provided cost estimate (See note above: for new structures, input 0). Click “Next”

4. Contacts -> Confirm contacts and add any additional contacts if applicable. Click “Next”

5. More Info -> This will be filled in by the engineer assigned to your case, Click “Next”

6. Attachments -> Please attach the project plan, supporting documentation for the cost estimate (if applicable), and a drainage/hydrology report (if applicable). Click “Next”

7. Signature -> Read the statement and type your name. Sign your name below (You may Enable Type Signature to have the software sign for you.) Click “Next”

8. Review and Submit -> Review all information to ensure accuracy. Click “Submit”

Contact Lianne Evans at lianne.evans@tucsonaz.gov or Stephen Blood at Stephen.Blood@tucsonaz.gov if you have any questions about the FUP.
08/31/2023 PDSD Application Completeness Express REVIEW COMPLETED