Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.4
Permit Number - TC-RES-0823-07683
Review Name: RESIDENTIAL SIMPLE REVIEW v.4
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/05/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/05/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0823-07683 (1751 W TENNYSON DR TUCSON, AZ 85746) 2nd Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC). Gas Plans: The following comments were not addressed. The size of the pipe is still undersized. 1. Size the pipe based on the length from the meter to the farthest attached appliance and max total demand of all attached appliances using Table G2413.4(1) (Metallic Pipe). Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1. 2. The ¾ inch pipe is insufficiently sized for the given demand and lengths. Minimum size required from the meter to the first split point, 1 ¼”. 3. The minimum size required from the first split point to the Range is 1”. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 09/05/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |