Permit Number: TC-RES-0823-07508
Parcel: 11708227B

Address:
37 W 19TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0823-07508
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/01/2023 Site Engineering NOT REQUIRED
09/18/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/06/2023 Residential Building REQUIRES RESUBMIT TC-RES-0823-07508
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The ADU requires a separate permit submittal under a separate address from the main dwelling. Each dwelling requires a separate utility shut off device and building drain clean-out.

GENERAL COMMENTS :

1. The main dwelling requires compliance with design ordinances for handicap, solar water, photo-voltaic, gray water and EV charging preparations. Design Ordinances adopted by the City of Tucson.
2. All plans submitted for a newly constructed one- or two-family dwelling after March 1, 2009, require a solar water system, or future installation preparation City of Tucson Ordinance #10549 with one of the following provisions: ½”control conduit and two ¾” copper piping for water with rooftop termination; straight 3” capped sleeve; or an accessible attic (clear path 30” wide x 30” high) over the water heater. Show appropriate notation.
3. Plans submitted for a newly constructed one- or two-family dwelling after July 1, 2009 require a solar photo-voltaic system, or future installation preparation City of Tucson Ordinance #10549 . Update breaker space to the last panel space.
4. Plans submitted for a newly constructed one- or two-family dwelling after June 1, 2010, must provide gray water utilization or preparation, Ordinance #10579/11089 revised July 9, 2013. The ordinance revision now requires a gray drain line discharge from one fixture for a one story dwelling. Additional gray fixture drains are optional. Show a second clothes washer standpipe plumbed to an exterior wall above grade when feasible, or a bathing fixture drain looped 3’ beyond an exterior wall below grade before connection to the building drain. Use the appropriate detail at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Water-Energy-Conservation
5. Show compliance with the Electric Vehicle Supply Equipment Ordinance adopted by the City of Tucson Ordinance #11844 on 6/22/2021. Include a 40 ampere 240 volt dedicated branch circuit with a NEMA 14-50R receptacle for charging an electric vehicle at a proposed parking space or show the distance from transit or a bike boulevard as not greater than a quarter-mile.

SITE PLAN:

1. Show the electrical panel with clear working space of 30” wide x 36” deep from panel face, E3405.2.

PLANS:

1. Show a maximum ½” floor elevation changes at a notated accessible route entrance on the floor plan, R106.1.1. Include the threshold condition at the vehicle doorway or an exterior hinged door when the garage is used for the accessible route.
2. Exterior walls with a fire separation distance less than 3-foot to the adjacent building with not less than one-hour fire-resistive construction. Show compliance with R302.1 (City of Tucson Amended) by providing a section detail of materials prescribed in IBC Table 721.1(2), Items 15-1.1 to 16-1.3. One dwelling requires a one-hour rated wall.
3. Indicate the direction of slope for the garage slab, R309.1.

PLUMBING PLANS:

1. Tucson Water Department limits flow rates for each water meter size in compliance with P2903.7. Show an appropriate yard pipe bypassing the existing dwelling and show the water meter size.

MECHANICAL PLANS:

1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation, or controlled exhaust with a calculated airflow rate, R303.4; N1103.6 & M1505.4. Show the system and appropriate flow rate setting on the plans. A two or three bedroom dwelling under 1501 SF requires a 45 CFM continuous setting.

ELECTRICAL PLANS:

1. TEP may require the service panel for the property at the closest building to the service transformer. A service line change or a new meter location must be coordinated with TEP for approval. Show an underground feeder from a new metered service panel to the more distant dwelling.
2. Update the Riser Diagram for the close dwelling and the feeder size to the detached dwelling panel per TEP coordination, NEC 225.30 and E3403.
3. Provide the Electric Vehicle Supply Equipment 40 ampere 240 volt dedicated branch circuit with a NEMA 14-50R receptacle and label the circuit “EV Ready” and locate the receptacle at a parking area, N1104.2.1. Include the Electric Vehicle load entry (typically 7680 watts) in the electrical load calculations (continuous demand) like the HVAC entry, N1104.2.2.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
09/18/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: Wyatt Berger
Lead Planner

PROJECT: TC-RES-0823-07508
37 West 19th Street – R-3
New single-family residence (1st Review)

TRANSMITTAL DATE: September 18, 2023

Please resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed.

1. A separate building permit is required for the proposed detached accessory dwelling unit (ADU). The scope of this specific review relates only to the proposed single-family residence.

2. A separate land division application is also required to divide the existing parcel into two individual parcels. The land split is required to be approved and recorded prior to zoning approval of this building permit.

3. Provide distances from the centerlines of 19th Street and 7th Avenue to north and west lot lines, as well as distances from the curb locations to the north and west lot lines to ensure setbacks are correctly depicted. Refer to Sheet 2 of Paving Plan I-480 for this information: https://maps-and-records.tucsonaz.gov/construction-plans/details/I-480.

4. Perimeter yard requirements are based on a measurement from the design grade elevation to the highest point of the exterior wall (UDC 6.4.5.B and Figure 6.4.5-A).

As measurements from the design grade elevation to the highest points of all exterior walls were not provided, an additional 0’-8” was added to the dimensions provided. Based on a wall height of 13’-2”, the required side perimeter yard setback is 8’-9”; proposed setback is 5’-6” as measured from the proposed south lot line.

Design Development Option (DDO) will be required to reduce the side perimeter yard setback. Ensure the land division application is approved and recorded prior to submittal of a DDO application. The DDO application and its requirements may be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/planning-amp-zoning/2019_ddo_for_setback_and_height_udc.pdf. Contact Georgia.Pennington@tucsonaz.gov if you have questions about the DDO process.

If you have any questions about this transmittal, contact me at Wyatt.Berger@tucsonaz.gov or at 520-837-4951.
08/30/2023 PDSD Application Completeness Express REVIEW COMPLETED This will only be in taken for the new SFR. Customer will need to submit separate permit for Adu. Customer was contacted to submit demo permit.