Permit Number: TC-RES-0823-07454
Parcel: 126060470

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.2

Permit Number - TC-RES-0823-07454
Review Name: RESIDENTIAL NEW DWELLING v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/30/2024 Historic APPROVED
02/15/2024 Site Zoning APPROVED
02/12/2024 Site Engineering NOT REQUIRED
02/15/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/30/2024 Residential Building REQUIRES RESUBMIT TC-RES-0823-07454 2nd

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet Zoning and other departmental requirements, conditions, and concerns before permit approval.

Living Room Addition with Basement, Loft and Deck for 940 N LONGFELLOW AV.

SITE PLAN:

1. Show the location and size of buildings, R106.1.1. Provide the added square footage of each addition area (basement, living floor, and loft).
2. Clarify the Live Load entries on the Project Data table (sheet A-1). Both the Floor and Deck entries should be 40 PFS.

PLANS:

1. Provide R311 compliant access to the roof deck. Update the ladder notation shown on sheet A-4 and A-9. A ladder access will require an appeal to the Building Official. https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/appeal_form4.pdf

STRUCTURAL PLANS:

1. Provide a complete roof framing plan with beams and rafters sized with appropriate prescriptive load carrying capacity, R301.1 or provide an engineer’s sealed plan set for performance compliance consideration, R301.1.3.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services