Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0823-07450
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/05/2023 | Site Engineering | NOT REQUIRED | |||
09/07/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
09/07/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | TC-RES-0823-07450 Resubmit comment: Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. Provide electrical load calculations for the subpanel showing the solar backfeed will not backfeed to the main panel, E3602.2, or Provide Main Service Panel (MSP) taps in compliance with NEC 705* (NEC 705.12) 705.12(B)(2)(3) b Busbars.) 120% bus bar rule. |
||
08/22/2023 | PDSD Application Completeness | REVIEW COMPLETED |