08/21/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/21/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed.
1. Submit a floor plan showing the new location of the water heater, make sure to indicate whether it is gas or electric (it has to be permitted and inspected as part this permit).
2. Show the required electrical panel clearances on the same drawing/floor plan, show the air handler on the plan confirming clearance is met.
3. Show the route of the emt on the roof, label it as such.
4. Show/indicate the grounding system that you are using.
5. Submit panel schedule for each panel.
6. Submit electrical load calculation.
Please resubmit