Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0823-07417
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/12/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/12/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | The plan review for the above-referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each notated item indicating the action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating the action taken, may be delayed until a response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. Your utility meter and the disconnect are located incorrectly in your line diagram. The utility meter and DG disconnect should be in between the combiner panel and the main service panel. NEC690.13 |
||
| 09/13/2023 | PDSD Application Completeness Express | REVIEW COMPLETED | |||
| 09/15/2023 | Site Engineering | REVIEW COMPLETED |