Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0823-07416
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/05/2023 | Site Engineering | NOT REQUIRED | |||
| 09/06/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/06/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | TC-RES-0823-07416 Resubmit comment: Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. Sheet PV03 Conductor tag 4 is undersized. Maximum conductor ampacity is determined by applying correction and adjustment factors for temperature of insulation rating of 90C and CCC (Current Carrying Conductor) proximity. Reference NEC 310.15, Table 310.15(B)(2)(a), 310.15(B)(2)(b) and 310.15(B)(3)(a). The adjusted conductor rating may not be less than the calculated Conductor Sizing. 2. For conductor tag 2, 10 awg wire is rated at 35 amps not 70 amps. 3. Update all conductor calculation table to correctly reflect the actual inverter current and the total number of currents carrying conductors in a conduit. R106.1.1 |
||
| 08/22/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |