Permit Number: TC-RES-0823-07319
Parcel: 129052540

Address:
3001 E 18TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0823-07319
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2023 Site Engineering NOT REQUIRED
09/25/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/30/2023 Residential Building REQUIRES RESUBMIT TC-RES-0823-07319
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. The plans require sufficient detail for demonstrating an awareness of minimum building code compliance for passing all progress inspections.

The submitted plan set includes construction information for a carport, west patio cover, east patio cover, and storage room.

SITE PLAN:

Provide a site plan showing the location of all buildings and utilities, R106.1.1. Show the location of electrical service panel and electrical lines between the panel and utility pole.

STRUCTURAL PLANS:

1. The carport does not show compliance with the 2018 IRC, therefore provide an Arizona structural engineer plan showing performance compliance for this structure, R301.1.
2. The west patio cover is sited within the 3foot fire separation distance from a property line. Show compliance with R302.1 (City of Tucson Amended) by providing a (barrier) wall with one-hour rated materials prescribed in IBC Table 721.1(2), Items 15-1.1 to 16-1.3, or remove the structure closer than 3 feet to the property line or remove the portion of roof projection closer than 2 feet from the property line along with (one-hour) fire rating the underside of the portion remaining in the 3foot fire separation distance.
3. The east patio cover appears 2018 IRC compliant.
4. The storage room requires a structural foundation. Show a complete cross-section detail of the new exterior wall, R106.1.1. Show the minimum 12” x 12” continuous #4 rebar reinforced footing, R403.1. Show with dimensions the exterior wood siding, insulation, interior sheathing, and pressure treated sill anchored with ½” x 10” bolts. Show the wall assembly with a 6” clearance above the ground or 2” clearance above an exterior concrete surface, R317.1 item 5.

ELECTRICAL PLANS:

1. Show any new or extended circuits serving outlet locations including receptacles, switches, and lights, E3902.

OUTDOOR LIGHTING CODE

Show the proposed fixture as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits. Adjustable security light fixtures are unshielded, not FCO.

If you have any questions, please contact:
Ken Van Karsen
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
08/22/2023 Site Zoning REQUIRES RESUBMIT 1. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Plan-Examples/Plot-Plan-Example, to include but not limited to:
a. The plot plan shall be drawn at an engineering scale.
b. For both Vancouver Pl. & Carson Av. provide a dimension from the center line to the face of curb, where pavement meets the concreate curb, and from face of curb to the property line. For Vancouver the distance from center line to face of curb is 15’, and from face of curb to property line is 10’. For Carson the distance from center line to face of curb is 18’, and from face of curb to property line is 12’. These dimensions are required to determine if the site wall has been built on site and not within the right-of-way.
09/25/2023 Zoning Modifications - DDO REQUIRES RESUBMIT The submitted DDO application has been deemed complete by Zoning Administration staff. If the DDO is approved, upload a copy of your DDO decision letter in addition to a revised plan set and comment response letter under existing permit number TC-RES-0823-07319.

Contact me at Wyatt.Berger@tucsonaz.gov if you have questions about the DDO process.
08/22/2023 PDSD Application Completeness Express REVIEW COMPLETED