Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/22/2023 | Site Zoning | APPROVED | |||
08/22/2023 | Site Engineering | NOT REQUIRED | |||
08/24/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
08/24/2023 | Residential Building | REQUIRES RESUBMIT | 1. Provide plans showing the correct address for each Single Family or Duplex dwelling address. (same plan set) 2. Show existing or proposed 1-hour rated wall between units, R302.4. 3. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3. 4. Show new or extended interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.16 & 17. | ||