Permit Number - TC-RES-0823-07305
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/07/2023 | Site Engineering | NOT REQUIRED | |||
| 09/07/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/07/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | The plan review for the above-referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating the action taken, may be delayed until the response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. Provide a lag-bolt connection up-lift calculation demonstrating the wind load-supporting capability, or provide an engineer’s calculation, and sealed design, R301.1, R324.4. An IRC PV roof uplift calculator (XLS) is available on Pima County’s website. https://www.pima.gov/1069/Solar-Wind-Systems 2. AC Overcurrent Protective Device and Conductor Sizing for PV source Circuits and Module Interconnection Conductors (Imax x 1.25) Reference NEC 690.8(A)(3) and (B)(1). The 15amp breaker in the combiner panel is undersized, provide a 20amp breaker. |
||