| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/14/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/14/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0823-07199 (9721 E 2ND ST TUCSON, AZ 85748) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC). 1. Conductor 4, between the Main Service Panel and the Sub Panel is undersized for the OCPD. Show the feeder connection, Sheet PV-03, complying with 705.12(B)(2)(1)(a) or (b). Ampacity of #8 CU, NEC Table 310.15(B)(16) 75 degree C, 40A. Load side OCPD, 150A. a. The feeder ampacity shall be not less than the sum of the primary source overcurrent device and 125% of the power source output circuit current (40A < 150A+21.15A). b. An overcurrent device on the load side of the power source connection shall be rated not greater than the ampacity of the feeder (150A > 50A). Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||