Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0823-07166
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/18/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/18/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | FROM: Veronica Flores PDSD Residential Review Section PROJECT: TC-RES-0823-07166 TOTAL PANELS: 10 TOTAL INVERTERS: 10 DC SYSTEM SIZE (kW): 4 kWAC SYSTEM SIZE (kW): 2.9 kW 200A MPU- (1st Review) (967 N VIA VERANO) TRANSMITTAL DATE: August 18th, 2023 Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. COMMENTS: Code reference, 2018 International Residential Code (IRC). 1. Fire rating requirements for modules on roofs next to a property line. R324.5.2, R902 fire rating listed as UL 790 or ASTM E108 2. .The conductor calculation table on sheet PV-03 Tag # 2 shows it receiving as 70 amps should be 35 amps. If you have any questions about this transmittal, Contact Veronica Flores any time during the week by email Veronica.Flores@tucsonaz.gov |
||
| 08/09/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |