Permit Number: TC-RES-0823-07143
Parcel: 112072430

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.8

Permit Number - TC-RES-0823-07143
Review Name: RESIDENTIAL NEW DWELLING v.8
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/26/2024 Residential Building REQUIRES RESUBMIT TC-RES-0823-07143 4th
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. Show the reference code on the site plan. The plans require sufficient detail for demonstrating an awareness of minimum building code compliance for passing all progress inspections.

Provide a response letter on separate file with the updated construction plan set.

Include all pages of construction plans into the single plan set. Place the response letter into separate file.

Provide a clear and concise construction plan set. Sample plans are available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits

SITE PLAN:

1. Provide the required square footages of existing and proposed buildings, R106.1.1. Place this sheet at page #1 in the plan set.

FLOOR PLANS:

1. Show the functional name of each room, R106.1.1.
2. Provide a landing or floor surface at all exterior doors. A landing is as wide as the door it serves and 36” in the direction of travel, R311.3.

STRUCTURAL PLANS:

1. Provide a roof framing plan with correct dimensions, beam, rafter and header sizes, R301.1.

SECTIONS - DETAILS:

1. Specify the anchor-bolt with length for assuring 7” embedment into concrete or masonry, R403.1.6. The ½” x 8” shown on sheet #5 is undersized.
2. An unvented roof assembly requires air-impermeable rigid insulation material of a minimum R-5 value applied correctly to either side of the roof sheathing as part of the total R-38 insulation requirement, R806.5. Note the elevation or provide an insulation detail showing spray foam or rigid foam board and batt layers. Verify rafter sizes with sufficient depth for the proposed insulation type.

MECHANICAL PLANS:

1. Provide heating facilities in all habitable rooms, R303.9. (Mini split, extend duct from a central HVAC or an electrical base board heater).

ELECTRICAL PLANS:

1. Provide a Riser Diagram showing a sub panel capacity and feeder size, NEC 225.30, E3403, Table E3704.2(1).
2. Provide a note stating interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights, and smoke detectors with combination type arc-fault circuit interrupters, E3902.16.

If you have any questions, please contact:
Ken Van Karsen
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
10/17/2024 Site Engineering REQUIRES RESUBMIT 1. This project is in a regulated City floodplain (Treat Ave Floodplain) and requires a floodplain use permit with elevation certificate. The base flood elevation is 2406.41ft NAVD88. The State of Arizona requires 1ft freeboard. The minimum FFE is 2407.41ft NAVD88. Clearly show this on the plans for the resubmittal and the floodplain use permit.

Mike Ortiz
michael.ortiz@tucsonaz.gov
10/18/2024 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Fernando Garcia
Planning & Development Services Department – Zoning Review Section

PROJECT: TC-RES-0823-07143 – Residential Building – One or Two Family
2517 E Alta Vista St, Tucson, AZ 85716
Building Plan Review (8th Review)

TRANSMITTAL DATE: October 18, 2024

This site is located in an R-2 zone (UDC 4.7.9). A single-family residence is a permitted use in this zone subject to use-specific standards 4.9.7.B.6, .9. and .10.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised plans, as noted in the comment below, along with a detailed letter indicating responses to the review comments.

Alert me by email to fernando.garcia2@tucsonaz.gov upon resubmittal for faster review.

See requirements for site/plot plans, including an example, at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Plan-Examples/Plot-Plan-Example

1. (Comment) The comment response letter indicates another set of revisions initiated by the owner to the plan. Submit a new set of organized plans that show all required information (including all information requested on previous plans) in one set of plans.

2. (Comment) Fully dimension all structures on the site plan; dimension all sides of the existing single-family residence (SFR) as well as the addition.

3. (Comment) Dimension all setbacks from existing and proposed structures to the adjacent property line(s).

4. (Comment) Label the height of both the walls and well as the roof on elevation drawings. Height is to be measured from design grade per UDC Section 6.4.4.

5. (Comment) Update all lot coverage calculations. Do not include porches in lot coverage. Do include any structures, as well as vehicular use areas like driveways.

6. (Comment) Show the entire property and label dimensions of all property lines.

7. (Comment) Although some of this requested information was previously requested – and may have been shown on previous plan submittals – it all needs to be consistently shown on all future submittals and changes to plans.

If you have any questions about this transmittal, please contact Fernando L. Garcia at fernando.garcia2@tucsonaz.gov.
09/19/2024 PDSD Application Completeness Express REVIEW COMPLETED