Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0823-07087
Parcel: 125122550

Address:
3310 E 4TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0823-07087
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/07/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0823-07087 (3310 E 4TH ST TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Provide the wire type and size for all electrical connections, E3404.13 & E3706.2. & NEC Table 5.
2. Provide the type of PVC, underground rated, conduit being used. This is needed for conduit fill calculations, NEC section 9 Table 5.
3. Provide a conduit fill calculation showing that 4x1/0 AWG Al and 6x14 AWG Al can fit in the provided conduit. Max fill for % for more than 2 conductors is 40%, NEC section 9 Table 1.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
08/07/2023 PDSD Application Completeness Express REVIEW COMPLETED