Permit Number: TC-RES-0823-07009
Parcel: 131100840

Address:
5542 E 24TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0823-07009
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/04/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0823-07009 (5542 E 24TH ST TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. The 10 AWG feeder conductor to the (N) Backup Sub Panel is undersized for the given main breaker (100A). Use NEC Table 310.15(B)(16) to size the feeder conductor correctly. OCPD for copper conductor 30A for #10 AWG, NEC 240.4(D)(small conductors)