Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0726-04256
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/03/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/03/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: 1. The submitted plans identify the service equipment as existing; however, previous permit records (TC-RES-1125-05423) indicate the service panel was not inspected and has since expired. Verify the service equipment currently installed on-site and revise the plans accordingly. If the existing service equipment was replaced, scope of work must be permitted prior to issuance of this building permit. If you wish to claim this as part of your scope of work, please identify the panel as "new" service equipment on the plans and demonstrate compliance with the surge protective device (SPD) requirements of 2023 NEC 230.67 and 2024 IRC E3606.5. Provide manufacturer specification sheets for the service equipment, including documentation demonstrating that the equipment is listed and configured for the proposed supply-side photovoltaic/ESS interconnection. |
||
| 07/31/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |