Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0726-04255
Parcel: 136090970

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-0726-04255
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/14/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please resubmit addressing the following comments:

1) Provide clarification regarding HVAC equipment sizing. The submitted Manual J identifies 1,730 ft² of conditioned floor area, while the dwelling is identified as 2,364 ft². The Manual J areas of 892 ft² and 838 ft² total 1,730 ft². Identify the remaining 634 ft² and clarify whether this area is conditioned or unconditioned. For equipment replacement, provide documentation supporting the conditioned floor area used in the Manual J calculation.

2) The proposed 3-ton and 4-ton systems shall be demonstrated to comply with 2024 IRC M1401.3 and 2024 IECC R403.7. Provide the Manual J cooling loads for each zone and corresponding Manual S equipment-selection calculations. Provide manufacturer/extended performance data identifying the sensible and total cooling capacities of the proposed equipment at the applicable design conditions. Revise the equipment sizing if the submitted Manual J/Manual S calculations do not support the proposed capacities.
08/13/2026 PDSD Application Completeness Express REVIEW COMPLETED