Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0726-04236
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/31/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please resubmit addressing the following comments:
1) A Surge Protection Device (SPD) or SPD model number must be identified on the plans for all service panel replacements supplying 100% of the dwelling. This requirement can be satisfied by providing the manufacturer’s specifications or model number for the SPD to verify that it is UL listed and code compliant E606.5 NEC 230.67
2) Upon resubmittal, please submit documents ONLY for the scope of this residential trade permit. The minimum requirement for residential trade permits for main panel upgrades are a site plan and SPD details (spec. sheet or model # along with the site plan).
07/30/2026 PDSD Application Completeness Express REVIEW COMPLETED