Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0726-04212
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/29/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/29/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: 1) Expand the one-line diagram to show the complete conduit routing from the subpanel to the new 20-amp GFCI receptacle/circuit. NEC 215.5, 300.4, 300.11 2) Revise the one-line diagram to identify the grounded (neutral) conductor and equipment grounding conductor (EGC) for all new branch circuits. NEC 200.4, 250.118, 250.121 3) Show the location of the new weatherproof box on the plans. Verify the enclosure is listed and suitable for installation in a wet location. NEC 314.15, 314.25, 406.9(B)(1) |
||
| 07/29/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |