Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0726-04210
Parcel: 110071340

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0726-04210
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/30/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please resubmit addressing the following comments:
1) ESS height inconsistent on elevation plan, height must be 48"+ to be considered protected from impact.
2) Clarify interconnection method adheres to 705.13 or 705.12(b)(2), show how monitoring will be measured for both ESS and PV. TC-RES-0225-00675 shows that PV is monitored using Enphase Power Control System controls while PW3 uses proprietary Tesla energy monitoring.
07/30/2026 PDSD Application Completeness Express REVIEW COMPLETED