Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/03/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please resubmit addressing the following comment:
1) See redlines on comment response letter. Height verified to be 48" above finished floor, please change 45" measurement on mounting diagram.
2) Provide CT location for Power Monitoring system to show power monitoring includes full site consumption to ensure PCS capabilities are accurate to the multiple power sources.
3) Provide Power Management (PCS) markings and plaque per 2023 NEC 750.30(C)(4) Marking.
07/31/2026 PDSD Application Completeness Express REVIEW COMPLETED