Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0726-04090
Parcel: 118120780

Address:
125 E 23RD ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0726-04090
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2026 Residential Zoning APPROVED
07/24/2026 Residential Engineering NOT REQUIRED
07/30/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/28/2026 Light Residential Building Review (OIP) - Standard REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please resubmit addressing the following comments:
1) A Surge Protection Device (SPD) must be identified on the plans for all service panel replacements supplying 100% of the dwelling. This requirement can be satisfied by providing the manufacturer’s specifications for the SPD to verify that it is UL listed and code compliant E606.5 NEC 230.67
07/23/2026 PDSD Application Completeness Express REVIEW COMPLETED