Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0726-04078
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/29/2026 | Residential Zoning | APPROVED | |||
| 07/29/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/28/2026 | Light Residential Building Review (OIP) - Standard | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: Service Panel Replacement 1) A Surge Protection Device (SPD) must be identified on the plans for all service panel replacements supplying 100% of the dwelling. This requirement can be satisfied by providing the manufacturer’s specifications for the SPD to verify that it is UL listed and code compliant E606.5 NEC 230.67 2) Show the location of the electrical equipment with clear working space compliance, working space must be WITHIN the property line 110.26(A) Structural Calcs 1) Plans show both tilted and flush-mounted PV equipment, please clarify which will be utilized 2) Show embedment of lag bolts to determine pullout resistance exceeds wind load. 3) Revise calculations to show calculations for each array, not all arrays contribute to the same roof plane. |
||
| 07/23/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |