07/22/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/22/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please resubmit addressing the following comments:

1) Verify the number of conductors required for the junction box to the new service panel adhere to conduit fill (shall not exceed 40% per 300.17 and Chapter 9 tables). Include EGC and grounded conductors.
2) Please provide the model # of the SPD to be install, SPD must have a nominal discharge current rating not less than 10kA, be UL 1449, and be Type 1 or Type 2. 230.67