Permit Number - TC-RES-0726-04050
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/22/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/22/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: 1) Verify the number of conductors required for the junction box to the new service panel adhere to conduit fill (shall not exceed 40% per 300.17 and Chapter 9 tables). Include EGC and grounded conductors. 2) Please provide the model # of the SPD to be install, SPD must have a nominal discharge current rating not less than 10kA, be UL 1449, and be Type 1 or Type 2. 230.67 |
||
| 07/22/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |