Permit Number: TC-RES-0726-04012
Parcel: 123022120

Address:
1902 N TUCKER DR

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-0726-04012
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/12/2026 Addressing Validation REQUIRES RESUBMIT If you have questions regarding the PDSD Application Completeness Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please submit a comment response letter demonstrating compliance with the following requirement:
1) Please provide both addresses to be powered by the dual meter pack on the site plan. Additionally, submit a change of address request to add the additional address to be powered by the dual meter pack so both addresses receive a proper clearance.
08/12/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please resubmit addressing the following comments:
1) A Surge Protection Device (SPD) or SPD model number must be identified on the plans for all service panel replacements supplying 100% of the dwelling. This requirement can be satisfied by providing the manufacturer’s specifications or model number for the SPD to verify that it is UL listed and code compliant E606.5 NEC 230.67
2) Please show scope of work to show all equipment installed, show where on the structure each service panel, meter, and supplemental equipment will be installed. Additional comments or permits may be required.
08/12/2026 PDSD Application Completeness Express REVIEW COMPLETED