Permit Number: TC-RES-0726-03968
Parcel: 11609312A

Address:
987 N LEUTEA DR

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.2

Permit Number - TC-RES-0726-03968
Review Name: RESIDENTIAL NEW DWELLING v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/21/2026 Residential Zoning APPROVED
11/09/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/09/2026 Fire New Construction Standard REQUIRES RESUBMIT *Per 2024 IFC Table B105.1(2), with the proposed construction type of V-B and a declared square footage of 5780sf (under roof), a fire flow of 2000gpm for 2 hours is required.
*Per 2024 IFC Table B105.1(1) for a single family residence greater than 3600sf that is sprinkled, 1/2 the value required by table B105.1(2) will suffice for a 1 hour duration. (ie. 1000GPM for 1 hour duration would be acceptable).
*Nearest hydrant is located 1000+ feet away (by approved fire department access roadway). Per 2024 IFC 507.5.1, Where a portion of of the building...is more than 400 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the building...
*Exception 1 to this reads: For group R3 and group U occupancies, the distance requirements shall be 600 feet (between the building and the closest hydrant).
*See 2024 IFC Appendix D for approved fire department access roadway specifications. Specifically maximum grade, width, turning radius, supportive roadway material, imposed loading requirements, and maximum length before requiring an approved turn-around for fire apparatus.

For questions or concerns regarding these, please reach out to me.

Ryan P Johnson
Tucson Fire Department
Fire Protection Plans Examiner
(520)539-5370
Ryan.Johnson@Tucsonaz.gov
10/20/2026 Residential Building REQUIRES RESUBMIT 1.Please provide detail drawings for the fire place and chimney per chapter 10 of the 2024 IRC.
2. Please show the beam spanning across the garage for detail #8 on S3.1.
3. Please show the beam spanning across the garage for detail #11 on S3.1.
4. Gutters and down spouts are not present on the plans, please show how rain water is being directed away from the foundation.
5. Please provide a detail of the guard railing per R321.
6. Please provide of hand rails per R320.
7. Please confirm FFE of proposed dwelling is above nearest man hole.
10/28/2026 Residential Engineering REQUIRES RESUBMIT Site Engineering Review

TC-RES-0726-03968
987 N LEUTEA DR
Date of Transmittal: 10/28/2026

Description: The scope includes a new single-family residence to replace the existing demolished residence.

City of Tucson Code:
https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes

Site Engineering comments are as follows:

1. The associated development package, TD-DEV-0926-00244, must be approved by all reviewers prior to the full approval of this residential building permit submittal. UDC Article 3.3.3.G.7.a
2. Address reviewers’ comments regarding the development package and the Residential Building reviewer’s concerns about this permit. Resubmit this permit once TD-DEV-0926-00244 is approved.
3. Additional comments may be forthcoming depending on the content of files submitted for subsequent review cycles.

*Please submit revised drawings / documents along with a detailed response letter stating how each resubmittal comment has been addressed*

To re-submit, visit the Tucson Development Center Online at:
https://cityoftucsonaz-energovweb.tylerhost.net/apps/selfservice#/home

Engineering Associate: Ryan Insalaco
ryan.insalaco@tucsonaz.gov
10/16/2026 PDSD Application Completeness Express REVIEW COMPLETED