Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0726-03962
Parcel: 10706063B

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-0726-03962
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/20/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this request, please email PDSD-Permits@tucsonaz.gov

1) The ¾” main line pipe is undersized for the given length and total appliance demand (200,000BTU). Size the pipe based on the length from the meter to the farthest attached appliance and max total Branch demand of all attached appliances using Table G2413.4(1) (Metallic Pipe). Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1. Please resubmit the gas template showing an adequate pipe size to this permit.

Step-by-Step instructions on how to resubmit:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf
07/20/2026 PDSD Application Completeness Express REVIEW COMPLETED