| 07/24/2026 | Residential Building - Standard | REQUIRES RESUBMIT | Please review the comments below and re submit. 1.Provide a Roof Framing Plan showing the beams and rafters sized for supporting live and dead structural loads usually obtained from the manufacturer. 2.An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. 3.E3606.5 Surge protection: all services supplying dwelling units shall be provided with a surge-protective device (SPD) installed in accordance with Sections E3606.5.1 through E3606.5.3. E3606.5.1 Location: the SPD shall be an integral part of the service equipment or shall be located immediately adjacent, if not located at each next-level distribution equipment downstream toward the load. |
||