Permit Number: TC-RES-0726-03952
Parcel: 133223910

Address:
7025 E LUANA DR

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADD/ALT v.1

Permit Number - TC-RES-0726-03952
Review Name: RESIDENTIAL ADD/ALT v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/28/2026 Residential Zoning APPROVED
07/23/2026 Residential Engineering NOT REQUIRED
07/28/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/24/2026 Residential Building - Standard REQUIRES RESUBMIT Please review the comments below and re submit.
1.Provide a Roof Framing Plan showing the beams and rafters sized for supporting live and dead structural loads usually obtained from the manufacturer.
2.An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5.
3.E3606.5 Surge protection: all services supplying dwelling units shall be provided with a surge-protective device (SPD) installed in accordance with Sections E3606.5.1 through E3606.5.3.
E3606.5.1 Location: the SPD shall be an integral part of the service equipment or shall be located immediately adjacent, if not located at each next-level distribution equipment downstream toward the load.