Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0726-03906
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/24/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/24/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov. Please address the following: During a subsequent review, it was determined that the approved plans do not comply with the adopted code requirements. The requirement to provide compliant working space for the electrical equipment was identified during the initial plan review; however, the submitted plans did not accurately demonstrate compliance with NEC 110.26(A). As a result, the issued permit will be revoked, and a new permit application with corrected plan documents will be required. Revise the site plan to show the location of the Energy Storage System (ESS) and associated disconnect(s) with the required working space located entirely within the property lines. Electrical equipment working space shall comply with NEC 110.26(A). Working space extending beyond the property line is not permitted. If you disagree with this code interpretation or this determination, the appropriate process is to submit a Building Code Appeal through TDC Online for formal review. Until an appeal is granted, the plans must demonstrate compliance with the adopted code requirements. |
||
| 07/24/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |