Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0726-03821
Parcel: 122181580

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-0726-03821
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/30/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact PDSD-Permits@tucsonaz.gov

Please resubmit addressing the following comments:
1) Eaton Type BR module surge does not meet code minimal. SPD must have a nominal discharge current rating not less than 10kA, be UL 1449, and be Type 1 or Type 2. 230.67
2) Please resubmit and provide a site plan or an aerial view with the address. Be sure to show the proposed location of the scope of work, this applies even if the location will remain the same.
07/30/2026 PDSD Application Completeness Express REVIEW COMPLETED