Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.2
Permit Number - TC-RES-0726-03821
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/30/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/30/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact PDSD-Permits@tucsonaz.gov Please resubmit addressing the following comments: 1) Eaton Type BR module surge does not meet code minimal. SPD must have a nominal discharge current rating not less than 10kA, be UL 1449, and be Type 1 or Type 2. 230.67 2) Please resubmit and provide a site plan or an aerial view with the address. Be sure to show the proposed location of the scope of work, this applies even if the location will remain the same. |
||
| 07/30/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |