Permit Number: TC-RES-0726-03797
Parcel: 136132440

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADD/ALT v.3

Permit Number - TC-RES-0726-03797
Review Name: RESIDENTIAL ADD/ALT v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/12/2026 Residential Building - Standard REQUIRES RESUBMIT Please review the comments below and re submit
1. Provide a Roof Framing Plan showing the rafters sized for supporting live and dead structural loads (Table R802.4.1(1)) or provide an engineer’s sealed plan set for manufactured trusses, R301.1.3.
2. Provide a wall section detail with (#4 rebar) reinforced 12” x 12” reinforced foundations for anchoring exterior framed (insulated) walls with pressure treated sills including ½” anchor bolts with 7” embedment, R403.1.6.
3. Identify the location and square footage of structural additions, R106.1.1.
4. Building and Wall Sections
Include all heights, materials of construction, fastening devices and related information.
08/11/2026 PDSD Application Completeness Express REVIEW COMPLETED