Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL ADU v.1
Permit Number - TC-RES-0726-03790
Review Name: RESIDENTIAL ADU v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/21/2026 | Residential Zoning | APPROVED | |||
| 07/21/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/15/2026 | Addressing Validation | REQUIRES RESUBMIT | For questions: PDSD-Permits@tucsonaz.gov The full address, including unit number 2, should be included on every page of the construction documents. After this initial review please resubmit the construction documents with full project address included. Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf |
||
| 07/16/2026 | Residential Building | REQUIRES RESUBMIT | TC-RES-0726-03790 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2024 International Residential Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. GENERAL REQUIREMENTS: The City of Tucson adopted the 2024 IRC with amendments and building ordinances for all dwellings. Provide a separate response letter addressing each comment with location of change on the plans. GENERAL COMMENTS: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Building-Codes 1. Show compliance with the Inclusive Home Design Ordinance adopted by the City of Tucson Ordinance #10463 on 10/16/2007. Notate accessible route, minimum door width, changes in floor elevation, door hardware, electrical outlet reach range, grab bar reinforcement, etc. 2. Plans submitted for a newly constructed one- or two-family dwelling after June 1, 2010, require gray water utilization or preparation, Ordinance #10579/11089 revised July 9, 2013. The ordinance revision now requires a gray drain line discharge from one fixture for a one-story dwelling. Additional gray fixture drains are optional. Show a dual clothes washer standpipe with a black connection and a gray line plumbed to an exterior wall above grade when feasible. Use the appropriate detail at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Water-Energy-Conservation Gray Water Illustrations SITE PLAN: 1. Show the location of the ADU supply water line connection between the existing dwelling and the meter, R106.1.1. 2. A 3-foot clearance above the roof for the existing overhead line may not be a feasible design, E3604.2.1. TEP may require the existing service panel for the property at the closest building to the service transformer. A service line change or a new meter location must be coordinated with TEP for approval. PLANS: 1. Notate a cool (white) roof finish (greater than 60 SRI) as required by the ADU provisions. 2. Clarify the location of keynote #20 on sheet A2.0. 3. Show a maximum ½” floor elevation changes at a notated accessible route entrance on the floor plan, R106.1.1. 4. Provide manufacturer’s calculations and data for pre-engineered trusses dated and wet-sealed by an engineer who is registered in Arizona, or notate the requirement for deferred submittal, R106.1. SECTIONS - DETAILS: 1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. Clarify the ceiling/roof insulation detail showing the air-impermeable rigid insulation material adhered to either side of the sheathing. Batt insulation may not be in contact with the roof sheathing. MECHANICAL PLANS: 1. Provide demand calculations in accordance with Manual J standards, M1401.3, M1601.1. 2. Provide whole-house mechanical ventilation with controlled exhaust, R303.4; N1103.6 & M1505.4. Identify the device model number providing an adjustable setting and note the minimum continuous setting. A one-bedroom dwelling under 1501 SF requires a 30 CFM continuous setting. 3. Provide makeup air of not less than 100 square inches where a clothes dryer is placed in a closet, M1502.6.1. PLUMBING PLANS: 1. Remove all outdated code reference from the fixture schedule. 2. Show the water heater rating/capacity for consistence with the electrical circuit size, R106.1.1. ELECTRICAL PLANS: 1. Update the smoke alarm circuit number and show on the panel schedule, R310. 2. Show a water heater circuit size for serving the load, E3702.11. 3. Verify if the dryer and range require a 240 volt double circuit entry, E3702.11. 4. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets, E3703.2 and E3901.3. 5. Provide GFCI protection for appliance receptacle outlets, E3902.12. Include: 1. Drinking water coolers 2. High pressure spray washing machines 3. Sump pumps 4. Dishwashers 5. Electric ranges 6. Wall-mounted ovens 7. Counter-mounted cooking units 8. Clothes dryers 9. Microwave ovens 10. Provide GFCI protection for receptacle outlets and HVAC equipment after September 1, 2026, E3902.14. OUTDOOR LIGHTING CODE 1. Show full cutoff fixtures were located within 25 feet from the property line OLC 401.3.3. INTERNATIONAL ENERGY CONSERVATION CODE: 1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans. If you have any questions, please contact: Kenneth.VanKarsen@tucsonaz.gov City of Tucson Residential Building Safety |
||
| 07/17/2026 | Residential Engineering | REQUIRES RESUBMIT | Permit Activity Number: TC-RES-0726-03790 (1st Review) Project: ADU with attached garage Location: 2021 E 10TH ST Unit: UNIT 2 Review Date: 7/17/2026 Reviewer: Marco Contreras – Engineering Associate - Site Engineering Reviewer Contact: Marco.contreras@tucsonaz.gov Related cases: Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed to ensure final approval from Site Engineering. To help speed up your resubmittal and facilitate shorter review timelines, please include a response letter along with your updated plans and any supporting calculations. In your response letter, address each comment individually and explain what changes were made and where they can be found in the plans. Please do not mark or highlight changes in the drawings at this stage — revision markups are only used after a permit has been issued. Submit your response letter and updated plan set as two separate files. Site Engineering Review Comments: 1. The City of Tucson Inclusive Home Design Ordinance requires all new dwellings — including ADUs, single-family residences, and duplexes — to provide an accessible route connecting the public street, sidewalk, or driveway to an accessible entrance of the home. This pathway must be shown, dimensioned, and labeled on the plans. What this means in plain terms: There needs to be a clearly defined, walkable path from where a person arrives (the street, sidewalk, or driveway) all the way to a usable door of the home — one that someone using a wheelchair or mobility aid could navigate without barriers. An exterior accessible route that shall conform to 2017 ICC A117.1 Sections 402 and 403 and City of Tucson Inclusive Home Design Ordinance. The current plans to no reference a material nor show a connection to ROW sidewalk or Parking area proposed. Ensure dimension the path at the minimum 4-feet required. 2. As currently shown, there is no direct accessible route proposed from the front door of the new Dwelling to the driveway nor to the garage/parking area. The plans currently show keynote #44 as vegetation. Revise accordingly. Reference: https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/inclusivehomedesignordinance.pdf Action Items — Show the following on your plans: • Draw and label the path as "Accessible Route" • Provide a minimum clear width of 4 feet with a width call-out on the plans • Note the proposed running slope (must not exceed 5% / 1:20) and cross slope (must not exceed 2% / 1:50) • Identify the accessible entrance the route leads to Acceptable Accessible Route compositions include: • Portland cement concrete (PCC) • Broom Finished concrete • Brick or unit pavers (Only if set on a stable cement base with no gaps exceeding ½”) • Concrete pavers on concrete base (Same joint and evenness requirements as brick) • Flagstone: must be mortared – loose set does not qualify • Any surfaces equivalent in smoothness, hardness, and durability NOTICE: Decomposed granite (DG) is not permitted for required accessible routes, even if compacted |
||
| 07/15/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |