Permit Number: TC-RES-0726-03752
Parcel: 130040990

Review Status: In Review

Review Details: RESIDENTIAL ADD/ALT v.1

Permit Number - TC-RES-0726-03752
Review Name: RESIDENTIAL ADD/ALT v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
N/A Bldg Permits - Post Review Express PENDING ASSIGNMENT
N/A Residential Engineering PENDING ASSIGNMENT
07/20/2026 Residential Building - Standard REQUIRES RESUBMIT TC-RES-0726-03752
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2024 International Residential Code and 2024 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2024 code compliance.

Place the current reference code on sheet A-1.

Construction plans require minimum code compliance for approval. The submitted plans are not compliant as documented with these comments and require alteration before approval.

Provide a separate response letter addressing each comment with location of change on the plans.

Provide a clear and concise construction plan set. Sample drawings are available for understanding details. Sample plans at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits

SECTIONS - DETAILS:

1. Provide a wall section detail with (#4 rebar) reinforced 12” x 12” reinforced foundations for anchoring exterior framed (insulated) walls with pressure treated sills including ½” anchor bolts with 7” embedment, R403.1.6.
2. Specify water-resistive barrier over the wood-based sheathing, R703.2.
3. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground (R317.1 item 5). The weep screed may extend with a minimum clearance 4” above grade or 2” above paved areas, R703.7.2.1.
4. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806. Attic space outside of the thermal barrier requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2 or an unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Identify the ventilation requirements and insulation types for complying with the condensation control issues.

MECHANICAL PLANS:

1. Provide heating facilities in the proposed room, R325.8. (Mini split, extend duct from a central HVAC or an electrical base board heater).

ELECTRICAL PLANS:

1. Show a smoke alarm in each bedroom and outside the doorway in the immediate vicinity, R310.3.2.
2. Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2.
3. Show at least one wall switch controlled light or outlet in bathrooms, hallways, stairways, attached garages, outdoor entrances or exits and all habitable rooms, E3903.3.
4. Interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights, and smoke detectors require combination type arc-fault circuit interrupters, E3902.16. Add notation to plans.
5. Show a wall-switch-controlled light fixture providing illumination on the exterior side of the egress door having grade level access R3903.3.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. The simplified prescribed energy values for glazing are U=0.40, skylights U=0.65, ceiling R=38 (R-30 for a qualifying room addition) and walls R=13. Show the “R” values of insulation and the maximum “U” factors of the windows and doors on the plans as well as the solar heat gain coefficient SHGC minimum value of 0.25, N1102.1.

OUTDOOR LIGHTING CODE

1. Show full cutoff fixtures were located within 25 feet from the property line OLC 401.3.3.

If you have any questions, please contact:
Kenneth.VanKarsen@tucsonaz.gov
City of Tucson Residential Building Safety
07/21/2026 Residential Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Erick Bieber
Planning & Development Services Department – Zoning Review Section

PROJECT: TC-RES-0726-03752
2362 E Warwick Vista, Tucson, AZ 85713
Residential Addition Alteration (1st Review)

TRANSMITTAL DATE: July 21st, 2026

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence is a permitted use in this zone subject to use-specific standards 4.9.7.B.6, .8, .9 and .12.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Correct plans, as noted in the comments below, along with a response letter indicating how all Site Zoning comments were addressed.

1. (Comment) The site plan provided is not sufficient. Please submit a site plan that meets the requirements found here: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Plan-Examples/Site-Plan-Examples

These requirements include but are not limited to:
a. Please show the entire lot on the site plan
b. Show all property lines and their dimensions, which are 125’ x 50’
c. Show all existing structures
d. Add the zoning classification, which is R-2
e. Label the adjacent street on the site plan
f. Show locations of existing utilities on the site plan

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code

For questions regarding Zoning comments, please contact me at: Erick.Bieber@tucsonaz.gov
07/15/2026 PDSD Application Completeness Express REVIEW COMPLETED