Permit Number: TC-RES-0725-03777
Parcel: 124110670

Address:
1637 E MILES ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING REVISION v.4

Permit Number - TC-RES-0725-03777
Review Name: RESIDENTIAL NEW DWELLING REVISION v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/16/2026 Residential Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-RES-0725-03777
ADDRESS/PARCEL: (1637 E MILES ST TUCSON, AZ 85719)
Submit your revised reports along with a response letter which states how all Building Review Section comments were addressed. The submitted documents were incomplete, and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter. Should you have any questions about these comments, I can be reached at ian.gillaspie@tucsonaz.gov.
COMMENTS:
1. Please provide a complete plan that includes section details for each wall, post, beam, and foundation condition, IRC R106.1. Clarify the roof framing design over the existing bedroom and bathroom near the rear of the home. The inspection performed on 3/6/2026 identified bearing walls removed under existing rafters. We need to see details explaining how the rafters will be supported.
2. Clarify the span of the porch beams from new post locations if posts will be relocated onto new porch footings IRC R106.1.
3. The walls at the rear of the building are proposed to be modified to extend the height of the roof and ceiling framing. Please Provide details ensuring these walls provide a continuous load path with lateral bracing, R301.1.
4. Please provide a header schedule that gives the complete dimensions of the 4x lumber being use at all windows, doors and openings.
5. Show compliance with R802.3 with continuous ceiling joist and collar ties in the upper third of attic space for hand-framed rafter conditions.
6. If the attic space is to be vented (per eave detail on sheet 3 of 7), please provide a ventilation calculation and show size and location of all vents to show compliance with R806.2.
7. Clearly indicate which mechanical supply and return vents and ducts are new and which are existing. Supply and return ducts must have a minimum of R-8 insulation if they are outside the thermal envelope (as in a vented attic space) N1103.3.3.
8. Smoke alarms must be interconnected by hardwiring to the building power source or through the use of listed wireless alarms R310.4 & R310.6.
9. Electrical panel schedule shows circuits 5&7 and 20&22 both as dedicated kitchen circuits, but only 20&22 are shown on the plans. Please clarify where 5&7 are located.
10. Show hot water pipe with minimum R-3 insulation, N1103.4.2.
11. Please correct and resubmit.
05/27/2026 PDSD Application Completeness Express REVIEW COMPLETED