Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0724-04471
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/06/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
08/06/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0724-04471 (1067 W MIRACLE MILE Unit:UNIT 87 TUCSON, AZ 85705) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). Notate the COT adopted code on the plan-set. 1. Provide a complete line diagram, NEC 110.2, 2018 IBC 107.1. Show the amp rating of the existing main service panel. A Registered Electrical Engineer is required when modifications are made to electrical designs that exceed 400 amps. 2. Provide electrical load calculations, for the Main Service Panel, Per NEC 220.40. 3. Provide an electrical riser diagram, 2017 NEC 230.9. Notate the grounding and bonding method for new sub-panel at unit 87, 2017 NEC 250.20(B), 250.24, 250.30(A)(4). Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
08/06/2024 | PDSD Application Completeness | REVIEW COMPLETED |