07/26/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0724-04367 (1419 E LINDEN ST TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. The ¾” pipe to the furnace and water heater is undersized for the given length and appliance demands.
2. Size the pipe based on the length from the meter to the farthest attached appliance and max total Branch demand of all attached appliances using Table G2413.4(1) (Metallic Pipe). Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1.
Given length, 85’, branch demand, 180,000 BTU. ¾” BIP is rated for 110,000 BTU.