Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.2
Permit Number - TC-RES-0724-04290
Review Name: RESIDENTIAL NEW DWELLING v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/27/2024 | Site Engineering | NOT REQUIRED | |||
| 08/27/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/01/2024 | Residential Building | REQUIRES RESUBMIT | TC-RES-0724-04290 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. GENERAL REQUIREMENTS: The City of Tucson adopted the 2018 IRC with amendments and building ordinances for all dwellings. Remove Pima County references. Provide a response letter on separate file with the updated construction plan set. GENERAL COMMENTS : 1. All plans submitted for a newly constructed one- or two-family dwelling after March 1, 2009, require a solar water system, or future installation preparation City of Tucson Ordinance #10549 with one of the following provisions: ½”control conduit and two ¾” copper piping for water with rooftop termination; straight 3” capped sleeve; or an accessible attic (clear path 30” wide x 30” high) over the water heater with attic access shown on the plans. Show appropriate notation. 2. All plans submitted for a newly constructed one- or two-family dwelling after June 1, 2010, must provide gray water utilization or preparation, Ordinance #10579/11089 revised July 9, 2013. The ordinance revision now requires a gray drain line discharge from one fixture for a one-story dwelling. Additional gray fixture drains are optional. Show a second clothes washer standpipe plumbed to an exterior wall above grade when feasible, or a bathing fixture drain looped 3’ beyond an exterior wall below grade before connection to the building drain. Show a bathing fixture drain looped 3’ beyond an exterior wall below grade before connection to the building drain when a clothes washer is not located at an exterior wall. Use the appropriate detail at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Water-Energy-Conservation Gray Water Illustrations PLANS: 1. Notate a cool (white) roof finish (greater than 60 SRI) as required by the ADU provisions. SECTIONS - DETAILS: 1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. Clarify the ceiling/roof insulation detail showing the air-impermeable rigid insulation material adhered to either side of the roof sheathing and the batt insulation in contact with the roof material. MECHANICAL PLANS: 1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation with controlled exhaust, R303.4; N1103.6 & M1505.4. Show the minimum airflow rate setting and location of the device requiring this adjustable setting. A two or three-bedroom dwelling under 1501 SF requires a 45 CFM continuous setting. 2. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D. ELECTRICAL PLANS: 1. Update the Riser Diagram showing the panel rating consistent with the panel schedule (100 AMP), E3601.6.2. INTERNATIONAL ENERGY CONSERVATION CODE: 1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans. If you have any questions, please contact: PDSD-Residential@tucsonaz.gov City of Tucson Residential Plan Review Submit a corrected plan set at https://www.tucsonaz.gov/pdsd |
||
| 08/19/2024 | Site Zoning | REQUIRES RESUBMIT | ZONING REVIEW TRANSMITTAL FROM: Wyatt Berger Lead Planner PROJECT: TC-RES-0724-04290 2201 North Margaret Avenue Unit 2 – R-2 ADU (1st Review) TRANSMITTAL DATE: August 19, 2024 The site is in the R-2 zone (UDC 4.7.9). An accessory dwelling unit (ADU) is a permitted use in the R-2 zone, subject to use-specific standards 4.9.7.B.6, .8, and .9, and 6.6.3. 1. According to the Pima County Assessor’s Office, the size of the property is approximately 7,505 square feet. Ensure the lot coverage calculations are amended to reflect the correct lot size. 2. Perimeter yards are based on a measurement from the design grade elevation to the highest point of an exterior building wall (see UDC 6.4.5.B and Figure 6.4.5-A). Per UDC Table 6.3-2.A, when a residential use is adjacent to a residential zone, the required interior perimeter yard is six feet or 2/3 the height of the exterior building wall, whichever is greater. Based on a wall height of 9’-6”, the required rear perimeter yard is 6’-4” as measured from the west lot line. The proposed rear perimeter yard is 6’-0”. A Design Development Option (DDO) is required to reduce the rear perimeter yard to 6’-0”. The DDO application and requirements can found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/planning-amp-zoning/ddo_for_setback_and_height_udc.pdf. Contact Georgia.Pennington@tucsonaz.gov or Mark.Castro@tucsonaz.gov if you have questions about the DDO process. 3. Label the dimension measured from the design grade elevation to the highest point of the post supporting the rear porch. A vertical structural member supporting a roof extension is considered a wall for applying perimeter yard requirements (UDC 6.4.5.B.2). Based on an assumed wall height of 10’-1”, the required side perimeter yard is approximately 6’-9” as measured from the north lot line. The proposed side perimeter yard is 6’-0”. A DDO will also be required to allow the side perimeter yard to be reduced. If you have any questions about this transmittal, contact me at Wyatt.Berger@tucsonaz.gov or at 520-837-4951. RESUBMITTAL OF THE FOLLOWING IS REQUIRED: A revised plan set as well as a comment response letter. To resubmit, visit the Tucson Development Center Online at https://tdc-online.tucsonaz.gov/#/home. The instructions for resubmittal can be found at https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf. |
||
| 07/25/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |