Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0724-04229
Parcel: 12006202A

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0724-04229
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/06/2025 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0724-04229 (32 E LINCOLN ST Unit:UNIT 2 TUCSON, AZ 85714)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Show compliance with NEC 690.15(A). The Disconnect Switch shall not be greater than 10’ from the service entrance and must be within sight. An appeal to the Building Official is required to waive this requirement.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
01/22/2025 PDSD Application Completeness Express REVIEW COMPLETED