Permit Number: TC-RES-0724-04217
Parcel: 115023740

Address:
210 E ELM ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0724-04217
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/19/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0724-04217 (210 E ELM ST TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

General:
1. Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. Contact sewer@pima.gov for review and assessment.
a. Provide PC RWRD permit and receipt.
2. Notify Pima County of the intent to remove/abandon the existing septic system. https://www.pima.gov/468/System-Closure-Abandonment. Provide confirmation that this has been completed.
3. Make the following, or equivalent, notes on the provided plans:
a. Remove all sewage from the facility and dispose of the sewage in a lawful manner;
b. Disconnect and remove electrical and mechanical components;
c. Remove or collapse the top of any tank or containment structure; and
d. Cut and plug both ends of the abandoned sewer drain pipe between the building and the onsite wastewater treatment facility

Plumbing Review:
4. Provide elevation measurements for Next Upstream Manhole cover and Finished Floor Elevation. Provide Backwater valve protection as/if required.
Backwater valve protection:
https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/building-code/2018_-_irc_amendments.pdf Section P3008.1 Where required. Where the finish floor elevation is less than 12 inches above the elevation of the next upstream manhole cover in the sewer, a backwater valve shall be installed in the building drain or branch of the building drain serving that floor.
5. Provide the Drainage fixture units for the main dwelling and the new ADU, P3004.1.
6. Show the new sewer line is sized per Table P3005.4.2.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
07/19/2024 PDSD Application Completeness Express REVIEW COMPLETED