Permit Number: TC-RES-0724-04018
Parcel: 11518138A

Address:
1249 N 13TH AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.2

Permit Number - TC-RES-0724-04018
Review Name: RESIDENTIAL SOLAR v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/30/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0724-04018 (1249 N 13TH AV TUCSON, AZ 85705)
2nd Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

Structural Review:

1. The updated structural calcs letter must be sealed by a registrant in the State of Arizona. The Florida Seal is not valid for projects in Arizona.

>>> These comments were not addressed.
2. Per the Sealed structural calcs letter, this project requires the following special inspections:
A: Helical/drilled piers foundation.
3. Provide a Special Inspection Certificate, with Parts A and B completed. https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
10/11/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-RES-0724-04018
1249 N 13TH AV. – R-2
GROUND MOUNTED PV SYSTEM (2nd Review)

TRANSMITTAL DATE: October 11, 2024

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-2 zone (UDC 4.7.9). A single family residence with ground mounted solar is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, 8, & 9 and 6.6.3.

1. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Plan-Examples/Plot-Plan-Example, to include but not limited to:
a. This comment was not addressed correctly. Review Unified Development Code (UDC) Article 6.4.3 and the example shown on the Residential Plot Plan Requirements and provide a complete lot coverage calculation. Provide a lot coverage calculation on the plot plan.
b. This comment was not addressed. Indicated the zoning of the property and all adjacent properties.
c. This comment was not addressed correctly. Per Construction Plan I-451 the distance from centerline of Mabel to the face of curb is 18’ and from face of curb to the north property line is 12’. Per Construction Plan I-77-033 the distance from centerline of 13 to the east property line is 30’-0” and the distance from curb to property line varies. Provide a dimension from the center line of all streets to be face of curb and from face of curb to the associated property line.
d. This comment was not addressed. Provide the legal description on the plan.

2. This comment was not addressed. Per UDC Article 6.6.3.C Detached accessory buildings , including accessory dwelling units , are not permitted in the buildable area extending the full width of the lot between the principal building and the front street lot line , except for shade structures or carports not over 400 square feet in floor area, terraces and steps not over three feet high above the natural grade, paved areas, and fences or walls. a Board of Adjustment for Variance will need to be submitted and approved.

3. This comment was not addressed. Per UDC Article 6.6.3.E The total gross floor area (gfa) of all accessory structures shall not exceed 50% of the gfa of the principal structure . Accessory structures less than 200 square feet gfa and accessory dwelling units are exempt from this requirement. Provide a calculation that either demonstrates that the 50% is or is not exceeded. If it is exceeded a Board of Adjustment for Variance will need to be submitted and approved.

As comments 5 & 6 require a Board of Adjustment for Variance comments 3 & 4 can be included in the Variance so that you do not have to go through two separate processes.

Board of Adjustment application/requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration. Contact for the Board of Adjustment is Mark Castro at Mark.Castro@tucsonaz.gov.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.